Products

F6150A Technical Specifications

F6150 Power System Simulator

Overview  Technical Specifications  Product Options  Software

Input Power: 95 to 264, VAC 47-63 Hz

Source Configurations:

Voltage Source:

Power and Range: 2x150 VA 75, 150, 300 V

4x75 VA 75, 150 V

Accuracy: < 0.02% typical

Each voltage source can be configured as a high power, low current range source to test high impedance ground/earth fault relays.

Power and Range: 2x150 VA 0.5, 1, 2 A

4x75 VA 0.5, 1 A

1x300 VA 1, 2, 4 A

Current Source:

Power and Range:

2x150 VA 7.5, 15, 30 A 4x75 VA 7.5, 15 A 1x300 VA 7.5, 15, 30, 60 A
Accuracy: < 0.02% typical

Each current source can be used in a transient mode which provides 50% more power at 2x current range.

Phase Angle:

0 to +359.9° (Lead)
0 to –359.9° (Lag)

Accuracy: < 0.1° typical

Frequency:

Range: dc to 3 kHz at full power

Accuracy: 0.5 PPM

Number of Logic Inputs: 8

Number of Logic Outputs: 8

Operating Temperature: 0° to 50° C

Enclosure: High impact, molded, flame retardant ABS – meets National Safe Transit Association testing specification No. 1A for immunity to severe shock and vibration.

Dimensions: 15 x 9.5 x 18 inches 38 x 24 x 45.7 cm

Weight: 37 lbs/16.8 kg (with front cover and carrying strap)

For assistance with Doble protection products and software, please email fserieshelp@doble.com.


Doble is an ISO 9001:2000 Certified Company. © 2012 Doble Engineering Company
All Rights Reserved. View our Privacy Statement.