OVERVIEW
Testing Applications
5 A-100 A (True DC), 0.1 µΩ resolution, Built-in memory and printer, Both Side Grounded for substation testing
Accurately measure very low contact resistances of switches and circuit breaker contacts, transformer and motor windings, wire and cable samples, joints in busbars, or any application where low resistance current is required.
MODEL |
MRM-100-V2 |
TEST CURRENT |
5 A – 100 A (True DC) |
RESISTANCE RANGES |
0.1 μΩ to 2 mΩ, with 0.1 μΩ resolution
2 mΩ to 300 mΩ, with 10 μΩ resolution |
RESOLUTION |
up to 0.1 μΩ |
INPUT |
100-240 V, 50/60 Hz |
BASIC ACCURACY |
±1% of reading from 50 μΩ to 300 mΩ |
Safety and Design Features
- Microprocessor controlled
- 4-wire Kelvin measurement
- Easy to read digital screen display
- IEC safety compliant
- ISO 17025 Calibrated (all models except MRM-10P)
OPTIONS & ACCESSORIES
Accessories Included
- Test Leads, 19’ (6 m), (optional lengths available) Set of 2 (combined current and potential), (1 red, 1 black) U terminal, C-clamp with opening of 80 mm (optional connectors available)
- Ground Test Lead (green), 10’ (3 m), U terminal, Alligator Clip with jaw opening of 20 mm
- Power Cord
- USB Cable, 6’ (1.8 m)
- Software license
- User guide
- Carrying Case for cables
Optional Leads-Model MRM100-V2 and MRM-200-V2
U Terminal and Clip
- Set of 2 (combined current & potential) (1 red, 1 black)
- Clip length 170 mm with opening 41 mm max
MAX CURRENT 100 A
- Optional lengths of 10, 20, 26, 32, 39, 49’ (3, 6, 8, 10, 12, 15 m)
MAX CURRENT 200 A