product

ALL VANGUARD CIRCUIT BREAKER POWER SUPPLIES

UPS S3
UPS S2
CB PWS
CBCT
FEATURES & BENEFITS
  • AC/DC adjustable output power supply designed to operate substation circuit breaker
  • Can supply up to 10 A during the circuit breaker coil energization and circuit breaker charging motor operation
  • Variable AC output voltage source (10-140 Vac) rated at 140 Vac @ 9 A continuous
  • DC voltage source (10-200 Vdc) rated at 180 Vdc@9 A (2 seconds) or 180 Vdc @ 2 A continuous
  • Both AC & DC voltage source outputs protected by a circuit breaker
TECHNICAL SPECIFICATIONS

PHYSICAL SPECIFICATIONS Dimensions: 17”W x 11.7”H x 12.5”D (44.5 cm x 30.0 cm x 31.8 cm);
Weight: 45 lbs (20.4 Kg)
INPUT POWER 100 – 120 Vac, 50/60 Hz
OUTPUT VOLTAGES DC: 10 – 200 Vdc
AC: 10 – 140 Vac
OUTPUT CURRENTS
9 A max @ 140 Vac (20 min on, 30 min off)
9 A max @ 140 Vdc (2 sec), 2 A (continuous)
DISPLAY Back-lit LCD screen (128 x 64 pixels); viewable in bright light and low light levels
SAFETY Designed to meet the UL 61010A-1 and CAN/CSA C22.2 No 1010.1-92 standards
TEMPERATURE Operating: -10° to 50° C (15°F to +122° F);
Storage: -30° C to 70° C (-22°F to +158° F)
HUMIDITY 90% RH @ 40°C (104°F) non-condensing
ALTITUDE 2,000 m (6,562 ft) to full safety specifications
CABLES Power cord, ground cable, 10′ (3.05m) test leads
OPTIONS Shipping case
WARRANTY One year on parts and labor
Specifications are valid at nominal voltage and ambient temperature of +25˚C (+77˚F).
Last updated on February 13, 2009

PART NUMBERS
  • 9140-UC [UPS S3 Unit and Cables]

2019 Circuit Breaker Seminar

Doble Engineering Company