product

ALL VANGUARD RELAY TEST EQUIPMENT

RFD-200 S3
PCI-600
FEATURES & BENEFITS
  • A built-in Timer displays contact time in both cycles and milliseconds
  • AC current source with 3 outputs (10A, 40A, 100A)
  • Set of NO/NC dry contacts that change state when a test is initiated
  • AC voltage source for testing relays up to 250 Vac
  • DC Voltage source (0 – 300 Vdc)
  • Volt meter input (0 – 600 V input range)
  • Three power supplies (24 Vdc, 48 Vdc, 124 Vdc)
  • Built-in power resistors
TECHNICAL SPECIFICATIONS

TYPEPortable relay test set
INPUT POWER100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50/60 Hz
PHYSICAL SPECIFICATIONS17”W x 12.5”H x 12”D, (42.7 cm x 32.0 cm x 30.5 cm); Weight: 35 lbs (15.9 kg)
AMPERE METER INPUT RANGESInternal input range: 0 – 250 A; Accuracy: 2% of reading ± 10 mA,
External AC input range: 0 – 6A; Accuracy: 1% of reading ± 10mA
External DC input range: 0 – 6A; Accuracy: 0.5% of reading ±1 count
Measurement Method: True RMS for AC
VOLT METER INPUT RANGE0 – 600.0V; AC accuracy: 1% of reading ±1 count; DC accuracy 0.5% of reading ±1 count
Measurement Method: True RMS for AC
AUXILIARY POWER SUPPLIES24 Vdc @ 1 A, 48 Vdc @ 0.25 A, 124 Vdc @ 0.125 A
POWER RESISTORS5 Ω/50 W, 1 Ω/50 W, 25 Ω/50 W, 100 Ω/50 W, 500 Ω/50 W
SAFETYDesigned to meet IEC61010 (1995), UL61010A-1, CSA-C22.2 standards
ENVIRONMENTOperating: -10˚C to 50˚ C (15˚F to +122˚ F); Storage: -30˚ C to 70˚ C (-22˚F to +158˚ F)
OPTIONSTransportation case
WARRANTYOne year on parts and labor
AC Current Output
RangeNo-Load VoltageLoad VoltageLoad CurrentLoad/Unload Times
10 A90 Vac75 Vac10 A2 min / 15 min
40 A25 Vac20 Vac40 A1 min / 15 min
100 A10 Vac7.25 Vac100 A1 min / 15 min
100 A10 Vac3 Vac250 A1 sec / 5 min
AC Voltage Output
RangeNo-Load VoltageLoad VoltageLoad CurrentLoad/Unload Times
250 Vac260 Vac240 Vac3 A10 min / 45 min
DC Voltage Output
RangeNo-Load VoltageLoad VoltageLoad CurrentLoad/Unload Times
300 Vdc300 Vdc250 Vdc2 A10 min / 45 min
RFD-200 Timer Second Display In seconds and cycles (50/60 Hz programmable)
RangeResolutionAccuracy
0 to 9.999 sec1 ms± (1 ms + 0.01%)
10.00 to 99.99 sec10 ms± (10 ms + 0.01%)
100.0 to 999.999 sec100 ms± (100 ms + 0.01%)
Timer Cycles Display
RangeResolutionAccuracy
0 to 9.999 cycles0.1 cycle± (0.1 cycle + 0.01%)
1,000 to 49,999 cycles / 50 Hz1 cycle± (1 cycle + 0.01%)
Specifications are valid at nominal voltage and ambient temperature of +25˚C (+77˚F).

PART NUMBERS
  • 9032-UC [110V RFD-200 S3]
  • 9082-UC [220V RFD-200 S3]

Doble Engineering Company

Doble Engineering Company