TYPE | Portable relay test set |
INPUT POWER | 100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50/60 Hz |
PHYSICAL SPECIFICATIONS | 17”W x 12.5”H x 12”D, (42.7 cm x 32.0 cm x 30.5 cm); Weight: 35 lbs (15.9 kg) |
AMPERE METER INPUT RANGES | Internal input range: 0 – 250 A; Accuracy: 2% of reading ± 10 mA, External AC input range: 0 – 6A; Accuracy: 1% of reading ± 10mA External DC input range: 0 – 6A; Accuracy: 0.5% of reading ±1 count Measurement Method: True RMS for AC |
VOLT METER INPUT RANGE | 0 – 600.0V; AC accuracy: 1% of reading ±1 count; DC accuracy 0.5% of reading ±1 count Measurement Method: True RMS for AC |
AUXILIARY POWER SUPPLIES | 24 Vdc @ 1 A, 48 Vdc @ 0.25 A, 124 Vdc @ 0.125 A |
POWER RESISTORS | 5 Ω/50 W, 1 Ω/50 W, 25 Ω/50 W, 100 Ω/50 W, 500 Ω/50 W |
SAFETY | Designed to meet IEC61010 (1995), UL61010A-1, CSA-C22.2 standards |
ENVIRONMENT | Operating: -10˚C to 50˚ C (15˚F to +122˚ F); Storage: -30˚ C to 70˚ C (-22˚F to +158˚ F) |
OPTIONS | Transportation case |
WARRANTY | One year on parts and labor |
AC Current Output |
Range | No-Load Voltage | Load Voltage | Load Current | Load/Unload Times | 10 A | 90 Vac | 75 Vac | 10 A | 2 min / 15 min | 40 A | 25 Vac | 20 Vac | 40 A | 1 min / 15 min | 100 A | 10 Vac | 7.25 Vac | 100 A | 1 min / 15 min | 100 A | 10 Vac | 3 Vac | 250 A | 1 sec / 5 min |
|
AC Voltage Output |
Range | No-Load Voltage | Load Voltage | Load Current | Load/Unload Times | 250 Vac | 260 Vac | 240 Vac | 3 A | 10 min / 45 min |
|
DC Voltage Output |
Range | No-Load Voltage | Load Voltage | Load Current | Load/Unload Times | 300 Vdc | 300 Vdc | 250 Vdc | 2 A | 10 min / 45 min |
|
RFD-200 Timer Second Display In seconds and cycles (50/60 Hz programmable) |
Range | Resolution | Accuracy | 0 to 9.999 sec | 1 ms | ± (1 ms + 0.01%) | 10.00 to 99.99 sec | 10 ms | ± (10 ms + 0.01%) | 100.0 to 999.999 sec | 100 ms | ± (100 ms + 0.01%) |
|
Timer Cycles Display |
Range | Resolution | Accuracy | 0 to 9.999 cycles | 0.1 cycle | ± (0.1 cycle + 0.01%) | 1,000 to 49,999 cycles / 50 Hz | 1 cycle | ± (1 cycle + 0.01%) |
|
Specifications are valid at nominal voltage and ambient temperature of +25˚C (+77˚F). |